Building Integrated Systems (BIS) was approached to develop a control system to reduce the exposure of N2O, commonly known as Entonox or ‘gas and air’.

In 2023, the government made hospitals aware of legislation limiting exposure to these gases, which are most frequently used during childbirth or occasionally as pain relief for some procedures.

The Cambridge University Hospitals NHS Foundation Trust conducted a clinical review. If the trust decided to continue with the use of gas and air, the risk of exposure by staff should be established through a risk assessment, with mitigations put in place where appropriate.

Addenbrooke’s was keen to monitor and mitigate occupational gas exposure levels through its building management system (BMS). This would protect staff by controlling the levels of N20 within each maternity delivery suite.

Work to monitor and mitigate danger.

Alongside the M&E consulting engineers JG Consulting, BIS developed a system capable of reducing the risk to staff and patients in Addenbrooke’s Rosie Maternity Units’ 15 delivery suites.

Gas detection system

Following meetings with the hospital and designers, BIS developed a strategy for the system. It decided on a centralised gas detection control panel, which was installed at the nurse station in the maternity department.

The panel was connected to the BMS using a RS485 Modbus RTU interface. This level of integration was a client requirement, allowing staff to obtain continuous logging of each gas sampler. Sensors were then polled every 15 minutes to obtain a value to record.

A gas sampler mounted in the suspended ceiling was located in each of the delivery suites. The design team selected this location because it avoided the possibility of the equipment being tampered with.

From this sampler, a tube was installed to a filter unit at each patient’s bed head, as this was deemed the best monitoring location. Each sampler was programmed to provide an output at a pre-determined setpoint to enable an extract fan in each room.

The fan was then used to extract the Entonox from the suite until the room returned to the required gas levels. A second output was also configured at each sampler to operate should the gas concentration continue to increase.

It was determined that if the gas continued to rise, this would indicate an issue with the ventilation system, triggering an alarm at the main control panel in the nurse station and also at the hospital maintenance BMS workstation.

Ventilation requirements

As mentioned, extract fans were installed in each delivery suite to keep the Entonox gas at the desired levels.

The BMS monitored the operation of the extract fans using a current switch, which provided an alarm if the fan was not operational.

Installation complexities

As the installation took place in a live maternity ward, BIS staff were required to work closely with medical teams to coordinate access. At times, this became complicated as rooms were not always available.

Also, there was sometimes a shortage of space, so work had to be paused to make room for treatment.

Results

Staff exposure to N20 gases is now successfully monitored and controlled as part of the building management system. The 15 delivery suites in the Rosie Maternity Unit are fitted with extract fans and remote systems to prevent over-exposure.

The system installed by Building Integrated Systems works seamlessly to protect and mitigate occupational N20 gas exposure.